Air-Cooled Condensing Units - Energy Technology List
1.1 Scope
Air-cooled condensing units covers products that are specifically designed to provide cooling to other equipment and systems that incorporate evaporators (and associated expansion valve control systems). Air-cooled condensing units are factory-assembled units that consist of an air-cooled condenser, one or more compressors, and interconnecing pipe work. They may include liquid receivers, filter driers, oil separators, shut off valves and related controls, and a weatherproof housing.
Kendall contains other products and information you need, so please check it out.
1.2 Definitions
An air-cooled condensing unit is a factory-assembled, packaged unit that consists of a refrigeration compressor, an air-cooled condenser and various ancillary components. This packaged unit does not contain a complete refrigeration system, but is designed to provide a convenient method for cooling a cold room or other equipment fitted with an evaporator that is controlled by an expansion valve.
Air-cooled condensing units are used in a variety of commercial and industrial cooling applications, including cold rooms, refrigerated display cabinets, back-bar equipment, temperature controlled food preparation areas, and for air conditioning systems.
Air-cooled condensing units are available in a range of different designs and efficiencies. The Energy Technology List (ETL) Scheme aims to encourage the purchase of the higher efficiency products.
The ETL Scheme covers products in three temperature categories:
- High temperature units.
- Medium temperature units.
- Low temperature units.
These categories are defined in terms of the product performance at a particular temperature rating point. Products may be submitted under more than one category.
To be eligible for inclusion on the ETL, products shall meet the requirements as set out below.
1.3 Requirements
1.3.1 Eligibility requirements
To be eligible, products shall:
- Be designed to operate with one or more clearly identified standard refrigerants.
- Be a factory assembled unit that incorporates at least the following components:
a) Air-cooled refrigerant condenser.
b) One or more electrically driven refrigeration compressors.
c) A control system that controls the products compressor(s) and cooling fan(s).
- Conform to the requirements of The Pressure Equipment (Safety) Regulations in respect of their design, manufacture and testing procedures.
1.3.2 Performance requirements
Products shall have a coefficient of performance (COP) or Seasonal Energy Performance Ratio (SEPR) that is greater than or equal to the values shown in Table 1.1, according to the rated cooling capacity of the product.
Table 1.1 Performance thresholds for air-cooled condensing units
Evaporating temperature (Dew point) Rated cooling capacity, PA (kW) Performance parameter Threshold Operating temperature HT +5°C n/a COP 3.4 MT -10°C 0 < PA 5 COP 2.0 5 < PA 20 SEPR 3.30 20 < PA 50 SEPR 3.30 PA > 50 COP 2.0 LT -35°C 0 < PA 2 COP 1.1 2 < PA 8 SEPR 1.70 8 < PA 20 SEPR 1.80 PA > 20 COP 1.1'' means 'greater than or equal to'
'' means 'greater than or equal to'
The COP, where applicable, should be measured at the specified standard rating points shown in Table 1.2.
Table 1.2 Testing conditions for COP of air-cooled condensing units at the standard rating points
Temperature category Evaporating temperature (Dew point) Ambient (Condenser air-on) temperature Compressor suction gas temperature High temperature units +5°C 32°C 20°C Medium temperature units -10°C 32°C 20°C Low temperature units -35°C 32°C 20°C
Where:
- COP = refrigerating capacity divided by the power absorbed.
- SEPR = reference annual cooling demand divided by the annual electricity consumption of the product
- Refrigerating capacity, power absorbed and reference annual cooling demand are as defined in BS EN: Condensing units for refrigeration Rating conditions, tolerances and presentation of manufacturers performance data.
- Any condenser sub-cooling factored into the refrigerating capacity shall be clearly declared, noting that when a liquid receiver is incorporated into the product with no subsequent sub-cooler, the liquid temperature at the unit outlet should be used to determine capacity.
1.4 Measurement and Calculations
1.4.1 Measurement standards
The following standards, where applicable, shall be used for measuring and calculating product performance:
- BS EN : Condensing units for refrigeration Rating conditions, tolerances and presentation of manufacturers performance data
- BS EN -2: Compressor and condensing units for refrigeration. Performance testing and test methods. Part 2: Condensing units
- BS EN : Refrigerant compressors. Rating conditions, tolerances and presentation of manufacturers performance data
Please note that performance data obtained in accordance with the test procedures set out in BS EN -2: will be accepted as an alternative to testing in accordance with BS EN -2: until further notice.
For product categories where a COP threshold is specified, performance data obtained in accordance with BS EN : will be accepted as an alternative to BS EN : until further notice.
1.4.2 Test Requirements
Product performance can either be determined using Method A or Method B to determine COP, or Method C to determine SEPR, subject to the following reporting requirements:
- For COP measurement, a detailed test report shall be provided and include a statement of achieved performance at the required standard rating point.
- For SEPR measurement, a detailed test report shall be provided for test point condition A or condition B according to the rating conditions defined in BS EN : Condensing units for refrigeration Rating conditions, tolerances and presentation of manufacturers performance data. In addition, a statement of performance at load conditions A, B, C and D, shall be provided. Where results are determined by calculation then this should be on the basis of design and/or extrapolation. In this case, details of such calculations and/or extrapolations, and of tests to verify the accuracy of the calculations undertaken shall be made available.
- The refrigerant properties used in the analysis of product / compressor performance shall be obtained from one of the following sources:
The US National Institute of Standards & Technology (NIST) Standard Reference Database 23 Thermodynamic and Transport Properties of Refrigerants and Refrigerant Mixtures Database: Version 6.0 or later. See http://fluidproperties.nist.gov/ or http://www.nist.gov/.
The ASERCOM properties database as defined in the ASERCOM Compressor Certification scheme, which is based closely on the NIST database (see http://www.asercom.org/). - For the high temperature category only, data for a suction gas temperature of 20°C may be obtained by the thermodynamic translation of data physically tested at 10K superheat.
- To enable calculations to be checked, the report shall include (or be accompanied by) the manufacturers design data for the product and its key components, including the type of refrigerant used, condenser fan motor power, and compressor make and model number.
1.4.3 Performance metrics
1.4.3.1 Method A to determine COP
Under method A:
- The products coefficient of performance (COP) at relevant standard rating point (as specified in Table 1.2) shall be calculated with the method used to generate its published performance over the standard range of air temperature and evaporating temperature conditions.
- The accuracy of these calculations shall be confirmed in the following manner:
a) Actual product performance should be determined at two test conditions close to the relevant standard rating point specified in Table 1.2 that comply with the following limits:
i. Evaporation temperature shall be within ±1°C of the standard rating point.
ii. Ambient temperature shall be within ±5°C of the standard rating point, and one point shall be above the standard rating condition, and one below it.
iii. Suction Temperature shall be within ±1°C of the standard rating point.
The following measurements shall be made at each test condition with the level of measurement uncertainty specified in Table 3 of BS EN -2: , whilst the product operating under stable conditions at full load:
i. Condensing and evaporating pressures and dew point temperatures at the compressor inlet and outlet.
ii. Superheat and sub-cooling at the compressors inlet and the products outlet.
iii. Condenser air inlet temperature.
b) The condensers UA value is determined at each test condition using the verified compressor performance data to establish the heat rejection rate.
c) The arithmetic mean of the UA values at the two test conditions is used to determine the condensing temperature, and the products performance at the standard rating point.
Are you interested in learning more about air cooled condensing units exporter? Contact us today to secure an expert consultation!
- The test report shall include (or be accompanied by):
a) Details of the calculation used to determine product performance.
b) The following information on the products compressor:
i. Refrigerating capacity and COP at the appropriate standard rating point specified in BS EN : , and at the relevant standard rating point specified in the eligibility criteria for refrigeration compressors.
ii. Evidence that the products compressor is listed on the Energy Technology Product List, or that its performance has been independently verified
iii. A copy of the manufacturers published performance data (or a print out of its key performance data from the manufacturers design/selection software).
1.4.3.2 Method B to determine COP
Under method B, product performance shall be demonstrated by testing the product in accordance with BS EN -2: Compressor and condensing units for refrigeration. Performance testing and test methods. Part 2: Condensing units.
1.4.3.3 Method C to determine SEPR
Under method C, product performance shall be demonstrated by testing the product in accordance with the procedures in BS EN -2: Compressor and condensing units for refrigeration. Performance testing and test methods. Part 2: Condensing units. The test conditions to be used, and the SEPR calculation method, should be those described in BS EN : Condensing units for refrigeration Rating conditions, tolerances and presentation of manufacturers performance data.
1.4.4 Rounding
For the avoidance of doubt COP test data should be presented to 1 decimal place. SEPR test data should be provided to 2 decimal places. As an example, a product in the high temperature category with a COP of 3.3 would be deemed to not meet the performance requirements.
1.5 Verification for ETL Listing
Any of the following testing routes may be used to demonstrate the conformity of products against the requirements:
- In-house testing Self-tested and self-certified
- In-house testing Self-tested and verified or cross-checked by an independent body
- Witnessed testing
- Independent testing
- Representative testing (see clause 1.5.1)
Further information regarding the first three routes can be found in the ETL Testing Framework.
1.5.1 Representative Testing
Where applications are being made for a range of two or more products that are variants of the same basic design, test data may be submitted for a representative selection of models, provided that all variants:
- Use the same refrigerant as the representative model.
- Have the same compressor type (i.e. manufacturer, method of compression (e.g. reciprocating or scroll) and type of enclosure (e.g. hermetic or semi-hermetic)) as the representative model.
- Have the same sub cooling arrangement as the representative model.
- Fit within the same product category (e.g. are all high temperature units).
The representative models shall be selected by dividing the range of products into groups of models with similar design characteristics, and testing a model in each group. The performance of each model in the group shall be predicted using a validated mathematical model. As a minimum, at least one model shall be tested in each range of products.
It should be noted that:
- If a manufacturer voluntarily removes the representative model from the ETL then other products linked with that representative model may or may not be permitted to remain on the ETL.
- If any product submitted under these representative model rules is later found not to meet the performance criteria when independently tested, then all products based on the same representative model will be removed from the ETL.
1.6 Conformity testing
Products listed on the ETL may be subject to the schemes conformity testing programme in order to ensure listed models continue to meet the ETL requirements.
1.7 Review
1.7.1 Indicative review date
This specification is scheduled for review during the /22 ETL review cycle.
1.7.2 Illustrative future direction of the requirements
As the use of new low Global Warming Potential (GWP) refrigerants becomes more widespread in the air cooled condensing units market, eligibility and performance requirements may be reviewed, to account for the range of new lower GWP refrigerants that will become more widespread due to the EU F-gas regulations. The performance parameters may also be reviewed; products could potentially be assessed on their overall environmental impact accounting for seasonal efficiency, refrigerant GWP and refrigerant leakage.
Air-cooled Condensing Units
When installing walk-in coolers and freezers, the installing contractor will need to select the proper location of the condensing unit. Location is an important consideration for the overall success of the installation. There are several items to consider when selecting the location.
First, the location should be discussed with the customer. Be sure the customer is in agreement with the placement of the condensing unit. The customer may have a plan for the location different from where the installing contractor decides to place the unit. As retail space becomes more expensive, customers will want to take advantage of all their indoor space and may want the condensing unit located outdoors or in an indoor location that will not interfere with their operation.
If the condensing unit is to be placed indoors, make sure the location has adequate ventilation. Low-temperature condensing units will require approximately 200 cubic feet per minute (cfm) per 1,000 Btu, and medium-temperature units will require approximately 165 cfm per 1,000 Btu. Always check with the condensing unit manufacturer for ventilation requirements, as they may differ from these approximate values. Another consideration with air-cooled units located indoors is the heat they may add to the space. This additional heat may be objectionable to the equipment owner.
OUTDOOR CONSIDERATIONS
An alternative to locating the condensing unit indoors is to place it outdoors. When installed outdoors there are several components that should be added with the condensing unit. Some of these components may be ordered as installed options.
The condensing unit should have a crankcase heater installed. This will help to prevent refrigerant migration during the off-cycle when the condensing unit is exposed to temperatures that are colder than the evaporator. The condensing unit will also need some means of keeping the high side pressure above a minimum value during low outdoor temperatures. This is normally accomplished with either a fan-cycling control or a head-pressure controller.
The method of controlling the case temperature may also need to be modified. The system should use a pumpdown method to control the operation of the condensing unit. A standard air-sensing temperature controller should be used to control the operation of a liquid line solenoid. When the temperature controller is satisfied, it will close the liquid line solenoid, causing the refrigerant to be trapped in the condenser and receiver.
This will cause the low-side pressure to drop. The system's low-pressure control will then shut down the condensing unit as the low side pressure drops to an appropriate value. A defrost timer will also need to be added to the control system to ensure that the evaporator defrosts properly.
The outdoor unit should be covered to protect it from the outdoor environment. If the condensing unit is ordered for an outdoor application, it will normally come with some type of enclosure. When moving an indoor condensing unit to the outdoors, make sure an adequate enclosure is constructed to properly protect the unit.
One last consideration when installing either an indoor or outdoor condensing unit is to make sure the system can be easily serviced. Too often, service technicians encounter systems in which the condensing unit is located in an area where it is extremely difficult to access. Also, make sure there is an electrical disconnect available to shut off the electrical supply when needed.