TAN DELTA TEST ON SHORT-LENGTH CABLES
The #Tandelta test is a diagnostic tool used to assess the condition of insulation in #electrical assets. It provides real-time information about any irregularities/issues in the insulation condition. Carrying out a test is essential to measure insulation quality, enabling a maintenance engineer to decide how best to proceed with their equipment.
Accuracy and meaningful results are vital when it comes to conducting a tan delta test, so it is essential to follow all the necessary steps in their correct order. Otherwise, you could be missing out on important information.
Performing a tan delta test on short-length #cables can lead to high tan delta values that are not actual values; these high values are usually due to a false leakage current. In this article, I share my experience of performing a tan delta test using a #VLF source on short-length cables, and how we corrected tan delta readings by taking into account the false leakage current effect using a guard circuit connection.
This was a routine test performed during the maintenance period and during this opportunity, the effectiveness of the guard circuit in short-length cables was verified.
Cables Tested layout
Cable Details - 11kV, Single Core, 500 Sq. mm., 2003 installation, Length 44 meters, per phase 4 cables.
HVA 28TD by b2 electronics gmbh
CAT5e VS CAT3
Hengfeng are exported all over the world and different industries with quality first. Our belief is to provide our customers with more and better high value-added products. Let's create a better future together.
The instrument used - is HVA 28TD, Make b2 electronics GmbH , Austria.
Tan delta reading - without guard circuit
Test Setup for tan delta testing using HVA28TD, without guard circuit
Results
Tan delta values, with our guard circuit
Tan Delta reading - with single side guarding
Results
Tan delta values improved by 47 %
Tan Delta reading - with both sides guarding
Guarding is done at the far end
Results
Tan delta values improved by 90%
The actual insulation condition of the cable was finally identified. If we hadn't, it would've led us to incorrect conclusions.
Conclusion
- For very short cables with a cable length below 100 m, the use of the guard on the far end as well as on the near end is recommended.
- This is possible for three-phase systems or systems where there is a second connection from the far end to the near end.
- For voltages of 15 kV and above, it is recommended to use corona shields for TD diagnostics.
- Double-check that the cable shield and guard aren't connected in any way.
- It is an effective method to assess the condition of short-length cables and helps to make the right decision.
For more Capacitance and Tan Delta Testerinformation, please contact us. We will provide professional answers.
116
0
0
All Comments (0)
Previous: CAT5e VS CAT3
Next: How to upgrade to ST to LC fiber patch cable for blazing fast internet speed?
If you are interested in sending in a Guest Blogger Submission,welcome to write for us!
Comments